IDA Districts 1.0.1 – Changelog

New Components

  • CarnotHpChillerIdealFlow
    Substation model for combined heating and cooling operation.
    • Includes two reversible pumps that draw flow either from the supply or return line depending on the operating mode (`hcmode`: heat pump / chiller).
    • The required mass flow is calculated automatically based on the current heating or cooling demand.
    • Performance is derived from the Carnot efficiency combined with a configurable real efficiency.
    • The component maintains the calculated mass flow under ideal flow conditions.
       
  • Bi2UniSwitchValve
    Bidirectional-to-unidirectional flow adapter.
    • Converts bidirectional flow into a controlled unidirectional flow.
    • The valve control signal determines the active flow direction and flow path.
       
  • HP_A2B
    Air-to-brine heat pump mode
    • Represents a heat pump using ambient air as the heat source and a brine circuit on the secondary side.
       
  • pow
    Mathematical signal-processing component.
    • Raises the input signal to a configurable exponent.
    • Can be used for custom control functions and mathematical relationships within the model.
       
  • GHX_Many – Borehole Field Model
    Three-dimensional ground heat exchanger model for arbitrary borehole field configurations.
    • Supports any combination of vertical or inclined boreholes with equal borehole length.
    • Based on the superposition of cylindrical 2D temperature fields around each borehole.
    • Includes a 1D vertical ground temperature field representing the undisturbed ground temperature and geothermal gradient.
    • Supports several symmetry options to reduce computational effort.
    • Includes Dirichlet boundary conditions at the top and bottom of the computational domain and an insulated outer boundary.
    • Accounts for ambient temperature, annual mean temperature and deep-ground temperature.

    • The model provides several temperature variables for detailed analysis, including:

      - **TUnDist** – Undisturbed ground temperature including the geothermal effect.
      - **DTref** – Ground temperature variation caused by climatic temperature variations.
      - **DT** – Temperature change caused by an individual borehole.
      - **DTSum** – Combined thermal influence of all surrounding boreholes on a specific borehole.
      - **TReal** – Actual ground temperature at the borehole locations.
      - **T** – Temperature field within a user-defined calculation plane.
       

Updated and New Templates

  • Low-Temperature Network
    The existing low-temperature network template has been extended and updated.
    • PE pipes are now available from the database.
    • Three different network configurations are provided.
    • A new third configuration introduces a **meshed network topology with two energy plants**.
    • The two plants are controlled dynamically according to the network load.
    • Waste heat integration has been added.
    • The previous star-shaped network configuration has been extended to demonstrate a meshed network topology.
       
  • Secondary Network
    New template demonstrating the interaction between a primary and secondary district energy network.
    • Includes two separate networks within the same simulation.
    • The primary and secondary networks are hydraulically separated by a heat exchanger.
    • Demonstrates energy transfer and interaction between two network levels.
       
  • Heating & Cooling Network
    New template combining a district heating network and a district cooling network.
    • Includes separate heating and cooling distribution networks.
    • The cooling network is designed with a smaller capacity and network size than the heating network.