Result – Systems energy

The report gives an overview of energy flows in the HVAC systems. It is divided into the following tables:

 

 

Used energy

Heat delivered by the plant and other heat generation/removal devices to the building distribution systems, i.e. presented flows may be reduced by distribution and emission losses before they reach their end use.

Utilized free energy

Heat at various points that can be considered free, due to recovery or extraction from a free source. Note that the same flow may be represented twice in the table, e.g. both when extracted from the ground and when recovered in the cold tank.

Generated electrical energy

Locally produced power. This energy is used within the building as far as possible. Only the surplus is sold..

Auxiliary energy

Energy for fans, pumps and similar.

Distribution losses

Energy which is partially or entirely lost within the distribution systems. Some of this heat may be usefully deposited in zones.

 

For cases with specified distribution losses, a separate table of distribution losses is presented.

 

Data for energy is presented in the following categories:

 

Used energy

category

comment

Zone heating

Heat delivered from the central plant or other, possibly local, heat generation devices to the zones. The distributed heat will normally be reduced by distribution and emission losses before it reaches the occupied space.

Zone cooling

D:o for cooling.

AHU heating

Heating energy supplied to all heating coils of central air handling units. No distribution losses are applied to the circuit between the plant and the AHU. The heating produced by electrical coils in the central AHU is included.

AHU Cooling

Energy removed by all cooling coils of air handling units. Note that a significant part of this energy may be latent due to condensation in coils. No distribution losses are applied to the circuit between the plant and the AHU. The cooling produced by electrical air conditioners in the central AHU is included.

Domestic hot water

Energy delivered to the domestic hot water circuit. The consumption rate is given in Extra energy and losses. Note that actual DHW end use may be smaller due to distribution losses.

 

 

Utilized free energy

category

comment

AHU heat recovery

Heating energy recovered in AHU air-to-air heat exchanger or mixing box.

AHU cold recovery

D:o for cooling.

Plant heat recovery

Heating energy that is fed into the hot tank from the brine circuit heat exchanger, e.g. chiller waste heat or direct exchange with another source connected to the brine circuit such as an ambient air heat exchanger.

Plant cold recovery

Cooling energy that is fed into the cold tank from the brine circuit heat exchanger, e.g. heat pump evaporator waste cold or direct exchange with another source connected to the brine circuit such as a ground heat exchanger.

Solar heat

Heat collected from a solar thermal collector.

Ambient heat

Heat extracted from an ambient air heat exchanger and which is fed to the brine circuit.

Ambient cold

Cold extracted from an ambient air heat exchanger and which is fed to the brine circuit.

Ground heat

Heat extracted from a ground source and which is fed to the brine circuit.

Ground cold

Cold extracted from a ground source and which is fed to the brine circuit.

 

Generated electrical energy

category

comment

Solar (PV)

Power generated by a photovoltaic unit.

Wind power

Power generated by a local wind turbine.

CHP power

Power generated by a local combined heating and power unit.

 

Auxiliary energy

category

comment

Humidification

Energy used by any central humidification equipment.

Fans

Energy used by fans. Fan electricity consumption is by default based on computed air flows and user supplied pressure heads and efficiencies.

Pumps

Energy used by pumps. Pump electricity consumption is by default based on computed water flows and user supplied pressure heads and efficiencies.

 

 

Data for the distribution losses overview is governed by coefficients specified in Extra energy and losses. Results are presented in the following categories:

Distribution losses

category

comment

Domestic hot water circuit

Heat lost from water in domestic hot water distribution systems, either due to permanent circulation or to intermittent tapping.

Heating

Heat lost from water in hot water distribution systems.

Cooling

Cooling energy lost from water in cold water distribution systems

Air ducts

Cooling energy lost from ductwork, both from transmission and air leakage.

 

A given percentage of each loss is emitted into zones according to floor area.

 

The data for report is collected by energy meter models (EMETER and EMETER2) that exist in Plant and AHU macros (for fans and pumps – in all macros). When defining custom Plant and AHU macros, the user should add the missing meter models and check (and fix, if required) the connections of EMETER.INPOWER with variables that calculate the power, as described in the table:

 

category

EMETER model

Typically connected to

Zone heating

Plant.EmeterLocalBoil

Q[2] in boiler model (type SIMBOIL)

 

EmeterLocHeat (automatically generated when building the advanced level system)

QLOCALUNITS in zone model (type CEDETZON and CESIMZON)

Zone cooling

Plant.EmeterLocalChil

Q2 in chiller model (type SIMCHIL)

 

EmeterLocCool (automatically generated when building the advanced level system)

QLOCALUNITS in zone model (type CEDETZON and CESIMZON)

AHU heating

AHU.EmeterHeat (in every central AHU and local AHU connected as central AHU)

QHEAT in heating coil (type HCSIMCTR)
Q in heating coil (type HCSIM)
QELACT in electric coil (type HCEL)

AHU Cooling

AHU.EmeterCool (in every central AHU and local AHU connected as central AHU)

QCOOL in cooling coil (type CCSIMCTR)
QTOTOUT in cooling coil (type CCSIM)

Domestic hot water

Plant.EmeterWater

QDOMWAT in chiller model (type SIMBOIL)

AHU Heat recovery

AHU.EmeterRecycle (in every central AHU)

QACTUAL in heat exchange model (type HXSIMCTR)

AHU Cold recovery

 

 

Plant Heat recovery

Plant.EmeterHotTank

QHX2TANK in hot tank model (type TANKSTRAT). Implemented in ESBO plant only

Plant Cold recovery

Plant.EmeterColdTank

QHX2TANK in cold tank model (type TANKSTRAT). Implemented in ESBO plant only

Solar heat

Plant.EmeterSolar

QU in solar collector model (SOLTHCOL). Implemented in ESBO plant only.

Ambient heat

Plant.EmeterAmbHX

Q in circuit control model (FREESUPCTR). Implemented in ESBO plant only.

Ambient cold

 

 

Ground heat

Plant.EmeterGrndHX

Q in circuit control model (FREESUPCTR). Implemented in ESBO plant only.

Ground cold

 

 

Solar (PV)

Plant.EmeterPV

P in PV model (PHOTOVOLT)

Wind power

Plant.EmeterWT

PW in wind turbine model (WINDMILL)

CHP power

Plant.EmeterCHP

PW in boiler model (BOIL1CIRC)

Humidification

AHU.EmeterHum (in every central AHU)

QEL in humidifier model (type STINJCTR)

Fans

AHU.EmeterFans (in every central AHU)

QSUP in fan model (type CEFAN)
PowerSup in axial fan (type AxialFan)

Pumps

Plant.EmeterPump

PPUMP in chiller, boiler, and pump models (SIMBOIL, SIMCHIL, PUMP, PUMPCIRC)