Energy report for an air handling unit

Last modified by WikiBot on 2025/03/20 14:10

Result – Energy report for an air handling unit

ice_diagram_result_AHU_energy.gif

The report gives an overview of energy flows in an individual AHU.

 

Data is presented in the following categories:

 

 

 

Category

Comment

Heating

Heating energy supplied to all heating coils.

Cooling

Energy removed by all cooling coils. Note that a significant part of this energy may be latent due to condensation.

Heat recovery

Heating energy recovered in AHU air-to-air heat exchanger or mixing box.

Cold recovery

D:o for cooling.

Humidification

Energy used by humidification equipment.

Fans

Energy used by fans.

 

The data for report is collected by energy meter models (EMETER and EMETER2) that exist in the AHU macro. When a custom AHU macro is built, the user should check (and fix, if required) the connections of EMETER.INPOWER to variables that calculate the power, as described in the table below.

 

category

EMETER model

Typically connected to

AHU heating

EmeterHeat

QHEAT in heating coil (type HCSIMCTR)
Q in heating coil (type HCSIM)
QELACT in electric coil (type HCEL)

AHU Cooling

EmeterCool

QCOOL in cooling coil (type CCSIMCTR)
QTOTOUT in cooling coil (type CCSIM)

Heat recovery

EmeterRecycle

QACTUAL in heat exchange model (type HXSIMCTR)

Cold recovery

 

 

Humidification

EmeterHum

QEL in humidifier model (type STINJCTR)

Fans

EmeterFans

QSUP in fan model (type CEFAN)
PowerSup in axial fan (type AxialFan)

 

The time evolution of the individual terms can be followed by selecting Log sources in the List of output objects.