Tables for Heating load simulation

Last modified by Bengt Hellström on 2026/10/20 13:27

Tables for Heating load simulation

The Zones table shows zone peak results of the last heating load simulation.

Find general information about the scalar results and Summary tab here Simulation results.

Zone

The zone name.

Group

The group name (assigned by the user or by the tool that created the model).

Room multiplier, M

The number of rooms with these conditions. The "TOTAL" row shows (where applicable) the sums over all zones counting with zone multipliers

Heat supplied

Maximal value of the total supplied heating power (both sensible and latent) delivered to the zone from mechanical and natural ventilation (including leaks and infiltration) and from local units (both convective and radiative). The peak time is given as a tool tip (and under Time if this variable is the set variable for Heating load).

Note that this is the actual heat supplied and not that which would be required to maintain a certain temperature. Make sure that the setpoint temperature has been fulfilled.

Time

The peak time for the variable chosen for the Heating load simulation, "Heat supplied" or "Room unit heat". Peaks are calculated separately for both these variables, but all other variables in the table get their peak values at this time. The chosen variable is shown in the column before the Time column and the other one after the Time column. 

Room unit heat

Maximal value of the heating power delivered to the zone by room units (both convective and radiative). The time for this maximum may be different from the total peak. The peak time is given as a tool tip (and under Time if this variable is the set variable for Heating load).

Temp.

Mean air temperature in the zone at the peak time of the chosen variable (see Time).

Op temp

Operative temperature at the position of the first occupant at the peak time of the chosen variable (see Time). Empty if no occupants in zone

Sup airflow

Mechanical air supply flow rate at the peak time of the chosen variable (see Time).

Sup airtemp.

The temperature of air supplied by mechanical ventilation (mean value in case of multiple supply ducts) at the peak time of the chosen variable (see Time). Empty if there was no air supply at that time.

Ret airflow

Mechanical air return flow rate at the peak time of the chosen variable (see Time).

Other sup airflow

Air supply flow rate from openings, open windows and doors, leaks, chimneys, and infiltration at the peak time of the chosen variable (see Time).

Other sup airtemp

The temperature of air supplied from openings, open windows and doors, leaks, chimneys, and infiltration at the peak time of the chosen variable (see Time). Empty if there was no air supply at that time.

Rel hum

Relative humidity of the air in the zone at the peak time of the chosen variable (see Time).

CO2

Concentration of CO2 in the zone at the peak time of the chosen variable (see Time).

PPD

Percentage of people dissatisfied at the peak time of the chosen variable (see Time). The value is an average for all the people present at that time (in one or more groups). It is empty if there is no occupancy at that time.

Envelope and thermal bridges

Heat gained through external walls, floors, roofs and through thermal bridges at the peak time of the chosen variable (see Time).

Internal walls and masses

Heat gained through internal walls, floors, ceilings and internal masses at the peak time of the chosen variable (see Time).

Window and solar

Net heat gain through external windows, i.e. through long and short wave radiation as well as via transmission trough pane and frame. Advected heat through open windows is included in Infiltration and openings. The value is presented at the peak time of the chosen variable (see Time).

Mechanical supply air

Sensible heat supplied by mechanical ventilation at the peak time of the chosen variable (see Time).

Infiltration and openings

Sensible heat supplied via air from leaks and openings. For systems with only mechanical exhaust ventilation, all supply air will be accounted for here at the peak time of the chosen variable (see Time).

Occupants

Sensible heat from people in the zone, i.e. excluding heat from perspiration, at the peak time of the chosen variable (see Time).

Equipment

Heat from equipment in the zone, e.g. computers etc., at the peak time of the chosen variable (see Time).

Lighting

Heat from artificial lighting at the peak time of the chosen variable (see Time).

Local heating units

Heat from controlled heating units, e.g. radiators, fan coils etc., at the peak time of the chosen variable (see Time).

Local cooling units

Sensible heat from controlled cooling units, e.g. chilled beams, fan coils etc., at the peak time of the chosen variable (see Time).

Net losses

Heat from pipes, ducts etc., the leakage from which has been defined in Extra energy and losses at the peak time of the chosen variable (see Time).

The last 11 columns are given both in W and in W/m2.

The Systems table shows the maximum total heating power that has been supplied by the systems to the building and the time for this peak. At this peak, individual contributions to air handling units, room units (zones) and for domestic hot water are specified.

The Air handling units table shows the peak heating point of each air handling unit.

AHU

The name of the air handling unit.

Heating

Heating power transferred by heating coils.

Time

The time of peak heating coil load.

Cooling

Cooling power transferred at time of peak heating.

AHU heat recovery

Recovered heating power in heat exchanger at time of peak heating.

AHU cold recovery

Recovered cooling power in heat exchanger at time of peak heating.

Humidification

Power required for humidification at time of peak heating.

Fans

Total fan power drawn at time of peak heating.

The Traded Energy table shows peak demand values and peak times for different energy meters. For more information about this table and  the Delivered energy table, see Tables for Energy and Custom simulations.