Other models
Previous (Air quality) | Back to Start | Next (References)
TABLE OF CONTENT
Other models
Tunnel water flow model: condensation, evaporation, seepage and drainage

In IDA Tunnel, water may enter the tunnel via condensation on tunnel walls, seepage through the wall or through explicitly defined water or vapor sources (an option for tunnel Equipment). Wall seepage is considered to be homogeneously radial, flowing into the tunnel from all directions and the advected heat will influence the temperature profile into the tunnel wall.
Once inside the tunnel, entering water will form a free water table, which may evaporate into tunnel air. The size of the water table may be controlled by the user through the parameters DesignmDrain and fWet. Non-evaporated water is regarded to be immediately drained from each tunnel segment. When the flow, mDrain, of this water equals the given parameter DesignmDrain, the area of the water table is regarded to be fWet times the tunnel inner wall area. At smaller flows, the wetted area tends linearly to zero as mDrain approaches zero. At flows larger than DesignmDrain, the wetted area stays constant. To define a wetted area which is independent of actual flow, select DesignmDrain to be considerably smaller than actual mDrain (but non-zero).
The drain flow gets three contributions
where
| mdrain | drain flow per tunnel length (kg/sm) | mDrain | |
| mseep | water seepage per tunnel length out of wall (kg/sm) | mSeep | |
| mcond | condensation/evaporation flow per tunnel length at wall (kg/sm) | Humf | |
| mcondAir | condensation in air per tunnel length (not in platform) (kg/sm). | mAirCond |
where
| C | humidity fraction (m3/m3) | ||
| C∙ fmol | humidity ratio (kg/kg) | xHum | |
| Csurf | humidity fraction on wall (m3/m3) | ||
| Csurf fmol | surface humidity ratio (temperature and pressure dep.) (kg/kg) | xHumSurf | |
| Uconv | convective heat transfer coefficient (see sec. 2.2.1) (W/ m2˚C) | UConv | |
| cpAir | specific heat of air (J/kg˚C) | CP_AIR | |
| pact | actual wet perimeter (m) | ||
| fmol | 0.62198 = ratio of molecular masses of water and air. |
where
| Csat | saturated humidity fraction in air (m3/m3) | ||
| Csat ∙fmol | saturated humidity ratio (kg/kg) | xHumSat | |
| ccond | coefficient for air condensation (kg/sm3) | CondensCoeff | |
| A | tunnel cross section area of (m2). | aTun |
The actual perimeter used pact in the computations of mcond is
| pact | if C > Csurf then p else pwet (m) |
where pwet is given by
if mdrain > 0
= 0 otherwise
| pwet | wet perimeter (m) | wetPerim | |
| p | physical perimeter (m) | ||
| τwet | time constant (s) | TauWet | |
| fwet | fraction of perimeter which is wet at design drain flow | fWet | |
| mdesign | design drain flow/meter (kg/sm). | designmDrain |
Critical velocity
The minimum steady-state velocity of the ventilation air moving towards the fire, the critical velocity, needed for removing the smoke and preventing backlayering is computed according to the Kennedy formula. In the tunnel section models this is done by solving the system
where
| VC | critical velocity (m/s) | VC | |
| Tf | average temperature of fire site gases (˚C) | Tf | |
| Tappr | temperature of approaching air (˚C) | ||
| Qfire | heat from fire directly to air (W) | ||
| ρappr | density of approaching air (kg/m3) | ||
| cpAir | specific heat of air (J/kg˚C) | CP_AIR | |
| A | cross section area of fire segment (m2) annulus area, not including the area blockage, such as vehicles (m2) | ||
| h | tunnel height in fire segment, default is hydraulic diameter but if parameter VCHeight set > 0 this value is used (m) (NFPA 502-2014 and 502-2017) height from the base of the fire to the tunnel ceiling at the fire, default is hydraulic diameter but if parameter VCHeight set > 0 this value is used (m) (NFPA 502-2023) | ||
| g | 9.80665 = acceleration of gravity (m/s2) | ||
| K1 | =Froude number factor = Frc -1/3 is a function of Qfire according to NFPA 502-2017. =Froude number factor = 4.5 -1/3= 0.606 according to NFPA 502-2014 and NFPA 502-2023. | ||
| Frc | Froude number. | ||
| Kg | 1 + 0.0374 ∙ |min(0, fslope)| 0.8 = grade factor | Kg | |
| fslope | slope in direction of moving air (%). |
The subject of critical velocity remains an area of ongoing research, and the suggested formulas have been revised in every published edition of NFPA 502 over the last decade. These formulas will likely change again in future editions of NFPA 502. Therefore, it is the user’s responsibility to stay informed about the applicability and limitations of the various critical velocity formulas. Some guidance on their applicability and limitations can be found in Annex D of the NFPA 502-2023 version.
The critical velocity according to (NFPA 502-2014) is presented by VC0 in the list of variables.
The critical velocity according to (NFPA 502-2017) is presented by VC in the list of variables.
The critical velocity according to (NFPA 502-2023) is presented by VC1 in the list of variables.
As output signal we compute the quotient between velocity of approaching air vappr (with sign) and critical velocity VC and VC1
| VCSignal | = | vappr / VC . | VCSignal |
|---|
| VCSignal1 | = | vappr / VC1 . | VCSignal1 |
|---|
Mold growth index
A mathematical model for mold growth on wooden materials [Hukka, Viitanen 1999] has been implemented. The growth is described by the mold index, which is used in experiments for visual inspections and is quantified as follows:
- no growth
- some growth detected only with microscope
- moderate growth detected with microscope (cover more than 10 %)
- some growth detected visually
- visually detected coverage more than 10 %
- visually detected coverage more than 50 %
- visually detected coverage 100%.
The model consists of a differential equation (with constraints) where effects of exposure time, temperature, relative humidity and dry periods are taken into account. Our interpretation of the model is described below where the mold growth index is set equal to zero initially.
if T < 0.1 or RH < RHcrit then
M = max(M, 0)
else
if M < 1 then
else
endif
M = min(M, Mmax)
endif
where
| M | mold growth index | mold | |
| t | time (days) | ||
| t1 | beginning of dry period (T < 0.1 or RH < RHcrit ) (days) | ||
| T | air temperature (˚C) | TAir | |
| RH | relative humidity (%) | relHum | |
| RHcrit | –0.00267·T3 + 0.16·T2 – 3.13·T + 100 if T < 20 else 80 (%) critical relative humidity favorable to initiation of mold growth | ||
| Mmax |
largest possible mold growth | ||
| tm | 7·exp(–0.68·ln(T) – 13.9·ln(RH) +0.14·W – 0.33·SQ + 66.02) = response time for initiation of mold growth (days) | ||
| tv | 7·exp(–0.74·ln(T) – 12.72·ln(RH) + 0.06·W + 61.50) = response time for visual appearance of mold growth (days) | ||
| k1 | 2/( tv / tm – 1) if M > 1 else 1 | ||
| k2 | max(0, 1 – exp(2.3·(M – Mmax ))) | ||
| W | wood species (0 = pine (used), 1 = spruce) | ||
| SQ | surface quality (0 = resawn (used), 1 = original kiln-dried). |
Ice build-up
Ice build-up is computed using an enthalpy formulation. We assume that the source water comes from the drain flow described in section 2.4. Further we assume that the ice forms half spheres at every Δx meter.
where
| Mice | mass of ice per tunnel length ≥ 0 (kg/m) | mIce | |
| mwatIn | mdrain · pwet/( fwet·p) = drain flow available for ice build-up per tunnel length ≥ 0 (see 2.4) (kg/sm) | ||
| mdrain | drain flow per tunnel length ≥ 0 (see 2.4) (kg/sm) | mDrain | |
| pwet | wet perimeter (m) | wetPerim | |
| p | physical perimeter (m) | ||
| fwet | fraction of perimeter which is wet at design drain flow | fWet | |
| mwatOut | water leaving per tunnel length ≥ 0 (kg/sm) | ||
| Hice | enthalpy of ice (J/kg) | ||
| Tice | temperature of ice (˚C) | TIce | |
| H(TwatIn) | enthalpy of drain flow (J/kg) | ||
| TwatIn | temperature of drain flow (˚C) | ||
| H(TwatOut) | enthalpy of leaving water (J/kg) | ||
| TwatOut | temperature of leaving water (˚C) | ||
| Tair | temperature of tunnel air (˚C) | TAir | |
| Twall | temperature of tunnel wall (˚C) | TWall | |
| αair | 2·π·r2/(p·Δx ) · α = heat transfer coefficient between ice and air (W/˚C m) | ||
| αwall | π·r2/((3·r/8)·Δx) · kice = heat transfer coefficient between ice and wall (W/˚C m) | ||
| α | heat transfer coefficient between wall and air (see 2.2.4) (W/˚C m) | Alfa | |
| kice | 2.2 = thermal conductivity of ice (W/˚C m) | ||
| Δx | distance between ice masses (m) | dxIce | |
| r | (3· Mice ·Δx/(2·π·ρice)) 1/3 = radius of spheres (m) | ||
| ρice | 917 = density of ice (kg/m3). |
The enthalpy function H(T) is approximated with linear functions within the two phases and a jump at the melting temperature such that the enthalpy of ice at melting is zero:
dH/dT = cpWat = 4187 (J/˚C kg) in the liquid phase (T > 0)
dH/dT = cpIce = 2060 in the solid phase (T < 0)
ΔH = 3.34·105 (J/kg) latent heat of solidification/melting (T = 0).
We have two equations but five unknowns (Mice, mwatOut, Hice, TwatOut, TwatIn), so three assumptions are needed to get a well defined problem. Three cases can be defined. Either there is no ice (case 0), water and ice (case 1) or just ice (case 2). In case 0 we set Mice = 0 and Hice = 0. In the other two cases three assumptions are made.
- TwatOut = 0
- TwatIn = max(0, Twall)
- Hice = 0 in case 1 and mwatOut = 0 in case 2.
In case 1 we get
to solve for Mice and mwatOut and in case 2
for Mice and Hice (Tice = Hice/cpIce).
Set
then the cases are executed as follows to generate continuous functions Mice and Hice:
if s < 0 and (Mice > 0 or mwatIn > 0) then
case 2 (Mice > 0, Hice ≤ 0)
else if s < 0 or (Mice = 0 and s > mwatIn·ΔH) then
case 0 (Mice = 0, Hice;= 0)
else
case 1 (Mice ≥ 0, Hice= 0)
endif.
Train motion
Our model for the train motion is based on the requirement that it can be computed before starting the simulation. This implies that some factors affecting the train motion, e.g. the drag force, are omitted. We believe these factors have a minor influence on the train motion. They are still computed during the simulation and affect the train power consumption. The main factors determining the motion in our model are:
- Maximum allowed acceleration and retardation of train max_acc, max_ret
- Maximum available power of train max_pow
- Mass of train totalMass, Km
- Rolling resistance of train A, B
- Speed at nodes between route segments rSeg.v0, rSeg.v1
- Maximum allowed speed in route segments rSeg.vMax
- Coasting rSeg.vCoast
- Route profile (slopes along route).
A route is divided into route segments. A default segmentation is defined by the presence of platforms (or sections marked to be platforms) along the route. However, the number of and size of segments can be manually edited (e.g., to limit the speed on some section). Route segments are defined by a number, start position, length, maximum speed, end speed and dwell time (at stations).
A starting train will initially accelerate according to max_acc. If the necessary power, increasing with speed, reaches max_pow then the acceleration will be limited accordingly. Slopes along the route also affect the necessary power and can thus prevent the train from reaching maximum allowed speed or decrease train speed.
If the train speed should decrease at the end of a segment (i.e. the end speed is lower than the actual maximum speed) the deceleration is modelled as follows. If coasting is allowed the train coasts until the speed decreases to the minimum coasting speed, then it starts breaking. If coasting is not allowed or the train speed is lower than the minimum coasting speed, the train is only breaking. The breaking is done with retardation max_ret. Slope and rolling resistance affect the coasting.
On each route segment the basic equations for determining the train motion are:
with constraints
and boundary conditions
at start of route segment
at end of route segment
where
| xveh | position of vehicle (m/s) | train.x | |
| vveh | velocity of vehicle (m/s) | train.x_dot | |
| aveh | acceleration of vehicle (m/s2) | train.x_dot_dot | |
| vmax | Maximum velocity in route segment (m/s) | rSeg.vMax | |
| amax | Maximum acceleration of vehicle (m/s2) | max_acc | |
| rmax | Maximum retardation of vehicle (m/s2) | max_ret | |
| Pmax | Maximum available power of train (W) | max_power | |
| v0 | velocity of vehicle at start of route segment (m/s) | rSeg.v0, rSeg.v1 | |
| vend | velocity of vehicle at end of route segment (m/s) | rSeg.v1 | |
| Floc | locomotive force (N) | LocF [kN] | |
| Fdrag | aerodynamic drag force (see 2.1.1) (N), ignored when calculating train motion | DragF [kN] | |
| Froll | (Aveh + Bveh· vveh) · Mveh = rolling resistance force (N) only used when coasting, otherwise ignored | RollF [kN] | |
| g | 9.80665 = acceleration of gravity (m/s2) | ||
| kmveh | kinetic energy coefficient | Km | |
| fslope | mean slope of tunnel | slope | |
| Mveh | train total mass (incl. passengers) (kg) | totalMass | |
| Aveh | coefficient (m/ s2) | A | |
| Bveh | coefficient (s-1). | B |
Note that the drag force Fdrag is neglected here and that the rolling resistance force Froll is included only for coasting computations.
The conditions on the velocity at nodes between route segments need not be completely satisfied. If limiting acceleration and power constraints prevents the train velocity at ends of segments from reaching the specified value it is accepted if it is smaller than specified velocity. Larger end velocities are not allowed, e.g. a train has to stop at a station, and will cause an error message (except the first segment of the route where the error will be fixed by decreasing the start velocity).
The solution to this problem for the train motion in a route is saved in three parameter vectors containing time, position and speed.
Fire throttling effect
The throttling effect refers to a tunnel fire's tendency to impede airflow. Certain sources of aerodynamic resistance, influenced by temperature, contribute to an overall increase in tunnel resistance as the fire's heat release rate rises. This effect primarily stems from the expansion of heated air and combustion products downstream of the fire, resulting in decreased static pressure at the fire location due to temperature elevation, air expansion, and acceleration within the tunnel. Subsequently, the static pressure increases owing to airflow deceleration caused by cooling at the tunnel wall downstream of the fire. Additionally, there is an augmented airflow resistance due to temperature stratification downstream of the fire. This stratification effect varies depending on the case and can typically be accurately determined using 3D CFD simulations. Among these effects, the first, the pressure drop occurring in a fire, can be analytically calculated using momentum and mass balance for the fire control volume.
The pressure drop is computed based on the following equation:
where c represents the upstream of the fire and h represents its downstream (Figure).
By selecting the auto calculation option, the fire pressure drop is automatically calculated using the above formula, which depends on the air velocity and fire power.

Back Layering length for tunnel fire under longitudinal ventilation
The concept of backlayering length was initially proposed in the context of a horizontal tunnel fire under longitudinal ventilation. In a longitudinally ventilated tunnel, if the ventilation velocity is smaller than the so-called critical velocity, buoyant smoke can oppose the forced longitudinal flow, eventually leading to the formation of a steady-state backlayering flow in the upstream region of the fire source.
The back layering length is computed using the following equation.
Here, V represents the air velocity approaching the fire, and Vcr denotes the critical velocity of the fire. H stands for the tunnel height, and if it is unspecified, the tunnel hydraulic diameter is utilized. Mathematically, the equation yields a negative value when the air speed exceeds the critical velocity. However, in practical terms, this does not indicate smoke back layering. Therefore, in IDA Tunnel, we set the backlayering length (BL) equal to zero under this condition. It's worth noting that this equation is derived from the study by Hu et al. (2008).
Inventory of models
Table 1 shows the central models that have been developed for the program and some of their parameters.
Table 1: Modelica Models in IDA Tunnel Library
| Model name | Function | Parameters |
| Entry | Entry portal | Tunnel area, loss coefficient |
| Branch | Junction | Tunnel areas in main and branch, angle between main and branch |
| RailSection, RoadSection | Tunnel /shaft section | Friction factor, discretisation, tunnel area, hydraulic diameter, loss coefficients at area changes, jet fan data, equipment data, fire data |
| Platform | Platform | Size dimensions, number of occupants |
| Plenum | Plenum | Size dimensions |
| Passage | Passenger passage | Number of gates (1 or 2), doors/gate, stochastic and intermittent passenger flows |
| Leak | Leak to ambient from platform | Opening area, height above floor |
| Portal | Portal between platform/plenum and tunnel | Loss coefficients |
| Recirc | Recirculation between tunnel entries | Percentage recirculating |
| FanDuct | Air supply/exhaust | Tunnel areas, loss coefficients |
| AxialFan | Axial fan | Fan curve (spline) |
| Damper | Damper | Loss coefficients |
| VFGiven | Given flow | Air volume flow |
| Filter | Filter particles | Air volume flow and filter efficiency |
| Heater | Heater | Temperature setpoint |
| SaccarNoz | Saccardo nozzle | Angle, momentum exchange coefficient |